Flow calculator 4–20 mA

DTWT · 4–20 mA loop → volumetric flow, low-flow cut-off
Current must be within 4–20 mA.
Qmax must be a positive number.
Calculated flow (square-root scale, with cut-off)
—
Breakpoints
I [mA] Linear volume Square root (ideal) Square root (cut-off)
Conversion characteristic
linear conversion square-root ideal square-root, with cut-off (actual output)

With orifice-plate (and most other DP) flow measurement, differential pressure is proportional to the square of flow: Δp ~ Q². The transmitter measures Δp and transmits it linearly as 4–20 mA, so the signal itself is linear with respect to Q², not Q. Converting back to volumetric flow therefore requires a square root: Q = Q_max · √((I-4)/16). A linear conversion would significantly underestimate flow at low readings and overestimate it in the mid-range — visible above as the gap between the dotted and dashed curves.

At low Δp (the bottom of the range) the measurement carries relatively large noise and sensor inaccuracy. The square-root scale amplifies this further — a small absolute change in Δp near zero causes a large relative change in the calculated flow. This is why a low-flow cut-off is defined: a threshold (typically 3–10% of Q_max) below which the calculated flow is no longer considered reliable, and the transmitter reports and displays it as zero.

The cut-off threshold is specified in % of flow, but the mA scale is linear with respect to Δp = (Q/Q_max)², so converting it to mA requires squaring: I_cutoff = 4 + 16 · (cutoff% / 100)². Below this current, the transmitter reports zero flow — visible in the chart as a vertical jump on the solid curve exactly at I_cutoff.

Flow reading on the plant still doesn't add up?

The calculator checks the maths. If the value in the control system still doesn't match reality, it may be wiring, calibration, transmitter configuration or scaling in the PLC — work for a loop check and troubleshooting.