Thermocouple K / J: temperature and voltage

Converts between temperature and thermoelectric voltage for type K and J thermocouples with the NIST ITS-90 reference functions — with or without cold junction compensation. For service, commissioning or checking a temperature input. Free, no sign-up; the calculation runs only in your browser.

Conversion

Reference junction: 0 °C

Type K Voltage
— mV

The number of decimals shown is not the accuracy of a thermocouple or a measurement.

Related tools: Pt100 / Pt1000 → · 4–20 mA calculator → · All tools →

The thermocouple temperature doesn't match reality?

The calculator checks the conversion. If the measurement still doesn't match, the cause is often polarity, the wrong cable, the type configured on the input or cold junction compensation — that is instrumentation, commissioning and troubleshooting work.

What a thermocouple measures

A thermocouple does not generate a "temperature" but a thermoelectric voltage E in mV. It depends on the temperature difference between the measuring junction and the reference (cold) junction — where the thermocouple wires connect to the terminals.

The NIST ITS-90 reference functions give the voltage against a reference junction at 0 °C. Check points: 0 °C = 0 mV; type K at 100 °C ≈ 4.096 mV; type J at 100 °C ≈ 5.269 mV.

Why cold junction compensation (CJC) exists

In practice the terminals of a measuring module are at, say, 25 °C, not 0 °C. The module therefore has to know their temperature and work out what the thermocouple would read with the reference junction at 0 °C.

Modern transmitters and PLC inputs often do this automatically. The calculator shows the step explicitly:

°C → mV:  E_measured = E(T_hot) − E(T_cold)
mV → °C:  E_hot = E_measured + E(T_cold);  T_hot = E⁻¹(E_hot)

Without CJC the cold junction is taken as 0 °C. Ignoring a cold junction at 25 °C makes a reading around room temperature about 25 °C too low.

How the calculator works

The voltage comes from the NIST ITS-90 reference functions per interval: type K −270 … 0 °C and 0 … 1372 °C (the positive branch adds an exponential term to the polynomial), type J −210 … 760 °C and 760 … 1200 °C.

Voltage to temperature solves the reference function numerically within the type's range (Newton's method safeguarded by bisection, bounded iterations) — no extrapolation beyond the range.

For type K near −270 °C the sensitivity is tiny (microvolts per °C), so a small voltage change there means a large temperature change.

Type K and type J

Each type has its own reference function and range:

  • Type K — Ni-Cr / Ni-Al alloys, reference function range −270 … 1372 °C,
  • Type J — iron / Cu-Ni alloy, reference function range −210 … 1200 °C.

Positive voltage corresponds to the standard NIST polarity of the type: the measuring junction is hotter than the reference junction. Wire colour codes differ between standards and are not covered here.

Note

The calculation uses the NIST ITS-90 reference functions for the ideal standard thermocouple characteristic. The result does not replace calibration, a tolerance check of the specific sensor, a polarity check, a check of the extension or compensating cable, a check of the CJC sensor or an assessment of the whole measuring chain.