15-minute demand calculator

Converts the energy of a 15-minute interval into average demand and evaluates peaks across a series of intervals. A technical tool for orientation — free, no sign-up; the calculation runs only in your browser.

One interval

Average demand over 15 minutes
— kW

Series of intervals

Enter the energy of consecutive 15-minute intervals, for example from a meter or data logger export.

One value per line or separated by semicolons. A decimal point or comma both work (2.5 = 2,5).
Any value you want to compare the result with. It is not a contracted capacity or a tariff rule.
Peak 15-minute demand
— kW
Mean of intervals
— kW
Peak − mean
— kW
Intervals above the limit
—
Highest exceedance of the limit
— kW

Average demand per interval

IntervalEnergy [kWh]Average demand [kW]Status

Got your maximum? See how it relates to your reserved capacity: Reserved capacity utilisation →

Don't know what causes your peaks?

Interval data can show which equipment creates the peaks and when — and whether it makes sense to address them through operations, control or an investment.

What 15-minute demand is

It is not an instantaneous peak lasting milliseconds, nor the highest value a clamp meter shows for a moment. 15-minute demand is the average power over a 15-minute interval — the energy drawn in the interval divided by its length.

Example: 5 kWh consumed over 15 minutes means 5 / 0.25 = 20 kW of average demand.

How it is calculated

The meter records the energy of each interval, and power is derived from it:

P_avg = E / t
t = 15 min = 0.25 h
P_15 [kW] = E_15 [kWh] / 0.25 = 4 × E_15 [kWh]

A short inrush is spread out in the 15-minute average. Loads that run together for longer show up in it in full.

Why it matters

Short periods when several loads run together can create peak demand even when total monthly consumption is not extreme. Typically these are:

  • motors and drives,
  • heating,
  • compressors,
  • charging of vehicles or equipment,
  • production equipment.

A monthly bill shows the total energy, not when or why a peak occurred. For that you need interval data.

What this does not tell you yet

A single maximum on its own is not enough to design:

  • battery storage (BESS),
  • PV,
  • an energy management system (EMS),
  • peak shaving,
  • a change of contracted capacity.

That needs interval data over a longer period and the operating context — what was running at the time, and why.

Metering, consumption and peak analysis, and a technical assessment of the next steps: Energy →

Note

This calculation is a technical tool for orientation. It is not a distribution operator's billing calculation, a legal interpretation of a tariff, an energy audit or a BESS or PV design, and it is not a guaranteed basis for changing a contracted capacity. An exact assessment depends on the metering data, the distribution tariff, the type of supply point and the operating pattern; how demand is measured and evaluated can differ between operators and countries.